After the successful trial in 2007, using totes of 35% hydrogen peroxide, JNB aided the facility in the engineering of a permanent peroxide feed system. The system includes a 2,600 gallon storage tank with I-beam supports mounted over complete containment for safety. The installation also includes a bulk filling station and all other necessary safety measures, eye wash, piping etc. Since the tank is located higher to sump level, peroxide is fed by simple gravity into the tower sumps. No pumping is necessary. The facility is able to receive bulk deliveries of 50% peroxide and thus save further on chemical costs. This design also eliminates any necessary handling of the peroxide material by operators. This system remains in successful operation to date.

Examples of peroxide case studies and information can be found here:
Other case studies can be found here: