Alcatel-Lucent, Whippany, NJ - Cooling Tower Peroxide Installation 2008

After the successful trial in 2007 at Murray Hill, NJ, the Whippany, NJ location ran a trial on their tower sets using peroxide as a total cooling tower treatment. Since the Whippany towers are located on the roof, the option of simple gravity feed was not available. JNB worked with site personnel to engineer a pumping feed system using the returnable, double-walled 375 gallons totes of 35% peroxide. A pumping skid was designed including all necessary safety considerations. The skid was piped up the both tower set sumps using a manifold and valving to control tower feed to either tower set. The system is designed with a water purge to ensure no peroxide is left in the feed line after the feed sequence has taken place.

To date, the peroxide feed system at Whippany has resulted in excellent biological and corrosion performance of the tower system. The Whippany tower system has historically been subject to high amounts of suspended matter circulation in the system and no filtration of the tower water is employed. These suspended solids were partially due to high amounts of precipitated matter and subsequent difficulty in maintenance of proper biological control. High amounts of necessary halogen biocides, in the past, have also contributed to additional corrosion products in the circulating water. The local sewer authority also has strict requirements on the types of corrosion inhibitors the facility is able to use. Peroxide was a natural fit since it breaks down into water and oxygen and is, by itself, a biocide and corrosion inhibitor.

Prior to implementation of a peroxide program, JNB worked with site personnel to ensure the partial softening of the makeup water was operational. This helped the facility to maintain a lower LSI in the tower system and decreased some of the suspended matter in the towers. Even with some suspended matter in the system, the peroxide has maintained biological control of the towers to <100 cfu/ml for bacteria consistently since installation. Keeping the tower essentially sterile, eliminates biological deposits and under-deposit corrosion. Scale adhesion to tower surfaces is also eliminated since no biological slime is allowed to form on system surfaces. Even with some of the challenges at this installation, corrosion rates for mild steel and galvanized coupons have been excellent at 2.00 mils per year and 0.02 mils per year on copper.



Examples of peroxide case studies and information can be found here:

 

Other case studies can be found here:

      
   
Home | About Us | Site Map | Additional Services | Water Treatment | Training